site stats

Determine mass flow rate of refrigerant

WebApr 7, 2024 · Refrigerant-134a is to be cooled by water in a condenser. The refrigerant enters the condenser with a mass flow rate of 6 kg/min at 1 MPa and 70°C and leaves at 35°C. The cooling water enters at 300 kPa and 15°C and leaves at 25°C. Neglecting any pressure drops, determine the heat transfer rate from the refrigerant to water. Webi.e., the flow of mass m through a surface per unit time t.. The overdot on the m is Newton's notation for a time derivative.Since mass is a scalar quantity, the mass flow rate (the time derivative of mass) is also a scalar quantity. The change in mass is the amount that flows after crossing the boundary for some time duration, not the initial amount of mass at the …

Answered: An ice plant using steam as refrigerant… bartleby

WebA Refrigerator is designed to operate using refrigerant R-513a and is required to remove 78 kW of energy from the evaporator if the operating condtions of the plant are as follows caiculate the required mass flow rate of the refrigerant assuming no losses: Give your arfswer in kg/hr Operating Conditions:- Compressor - Inlet condition 1 bar dry ... WebQuestion: Determine; (1) The mass flow rate of the refrigerant through the lower cycle. kg/s (2) The rate of heat removal from the refrigerated space. (1) kW (3) The compressor power input. kW (4) The COP of the cascade refrigerator. (1)Determine; (1) The mass flow rate of the refrigerant through the lower cycle. kg/s (2) The rate of heat removal from … dan mcclough corning https://brazipino.com

Refrigeration Cycle - Simon Fraser University

Webh = heat of compression (Btu/lb) q = refrigerant circulated (lb/min) Compression Horsepower. Compression horsepower can be expressed as. P = W / 42.4 (2) where. P … Webcycle takes place in an adiabatic counter flow heat exchanger where both streams enter at about 0.32 MPa. If the mass flow rate of the refrigerant through the upper cycle is 0.05 … WebThe mass flow rate of the refrigerant is 0.08 kg/s. Determine (a) the compressor power, in kW, (b) the refrigeration capacity, in tons, (c) the coefficient of performance, and (d) the coefficient of performance of a Carnot refrigeration cycle operating between warm and cold regions at 26 and 0°C, respectively. dan mc clean psycologist amherst

Answered: A heat pump with refrigerant-22 (R-22)… bartleby

Category:Answered: A refrigerator uses refrigerant-134a as… bartleby

Tags:Determine mass flow rate of refrigerant

Determine mass flow rate of refrigerant

Answered: A commercial refrigerator with… bartleby

WebThe rate of refrigeration of the cycle is to be 10.55 kW of refrigeration. Determine the coefficient of performance of the device as a refrigerator and the mass flow rate of R … WebThe mass flow rate of the refrigerant was found to be 0.68 kg/s. The power input to the compressor was found to be 32.96 kJ/s. The mass flow rate of the cooling water was found to be 3.98 kg/s. The rate of exergy destruction associated with the compression process was found to be 7.84 kJ/s assuming a dead state temperature, T0, of 25 C.

Determine mass flow rate of refrigerant

Did you know?

WebWhile calculating the mass flow rate (MFR), pressure, enthalpy and entropy from temperatures at various state of Refrigerant R134a thermodynamic properties... WebAlso use Fundamentals of. (a)Determine the mass flow rate of refrigerant, in kg/s. (b)Determine compressor power in kW. (c)calculate coefficient of performance (use answer of part b to help you out.) Also …

WebJan 1, 2004 · A correlation was developed for mass flowrate of R12, R134a, R502, R22, R407C, and R410A through short tubes. Sort tube lengths ranged from 9.5 mm to 25.4 … http://www.jmcampbell.com/tip-of-the-month/2011/11/compressor-calculations-rigorous-using-equation-of-state-vs-shortcut-method/

WebJun 5, 2024 · How to calculate the mass flow rate of refrigerant passing through an evaporator with a given quality, pressure, and temperature of air mixture, using refrig... WebThe refrigerant enters the condenser at 12 bar and 50 °C and leaves at the same pressure subcooled by 8.25 °C. If the compressor consumes 8 kW of power, determine a) The mass flow rate of the refrigerant, b) The refrigeration load, c) The COP, and d) The minimum power input to the compressor for the same refrigeration load.

WebMay 10, 2024 · It is compressed isentropically to pressure of 1100 kPa, condensed at constant pressure and sub-cooled by 3 deg C. Finally it is expanded at constant enthalpy …

WebIf the compressor consumes 6.26 kW of power, accordingly determine a) The mass flow rate of the refrigerant, b) The rate of heat supply, c) The COP, and d) The minimum power input to the compressor for the same rate of heat supply. Note: You may use Thermodynamics Tables by Michael J. Moran for this question. dan mccolm countdownWebREFRIGERANT FLOW RATE . refrigerant flow rate = − Cooling Load H 2 H 1. COMPRESSOR . The work done on the refrigerant during the compression step is the . rate of work . done on the = (refrigerant flow rate ) (H3-H2) compressor . CONDENSER . The heat rejected to the environment in the condenser depends upon the . Pressure … birthday gifts 60 year old womanWebMar 23, 2024 · About Press Copyright Contact us Creators Advertise Developers Terms Privacy Policy & Safety How YouTube works Test new features NFL Sunday Ticket Press Copyright ... dan mccormack baysvillehttp://rpaulsingh.com/lectures/refrigeration.pdf dan mcconaughey trainingWebSince no mass flow rate of the refrigerant has been provided, the entire analysis is done in terms of specific energy values. Notice that the same system can be used either for a refrigerator or air conditioner, in which the heat absorbed in the evaporator (q evap ) is the desired output, or for a heat pump, in which the heat rejected in the ... birthday gifts 2 year old femaleWebThe refrigerant enters the condenser at 1.2 MPa and 50°C and leaves at the same pressure subcooled by 5°C. If the compressor consumes 3.3 kW of power, determine (a) the mass flow rate of the refrigerant, (b) the refrigeration load, (c) the COP, and (d) the minimum power input to the compressor for the same refrigeration load. dan mccluskey steakhouse websiteWebFeb 7, 2010 · An ammonia refrigerating plant operates between temperature limits of 10.34 bar and 2.265 bar. The refrigerant leaves the evaporator as a vapour 0.95 dry and leaves the condenser as a saturated liquid. If the refrigerant mass flow rate is 4 kg/min, find: … The model of the expansion valve neglects heat losses, i.e. constant enthalpy is … birthday gifts 2 year old ideas boy